Condenser coil replacement in West Covina: old leaking coil removed from a Lennox rooftop unit and set on the roof

Case Study 005 · Commercial · Los Angeles CountyCondenser coil replacement
on a rooftop unit in West Covina.

A Lennox rooftop unit had stopped cooling because its condenser coil was leaking in a spot that could not be repaired. Here is the whole condenser coil replacement, photo by photo, from the old coil coming out to 58.1°F supply air.

COMMERCIAL · ROOFTOPSEP 5, 20259 PHOTOS FROM THE JOB
  • 2 daysFrom quote to new coil
  • R-410ACharge weighed in
  • 58.1°FSupply air after repair
  • 24.3°FTemperature split
// The job

Condenser coil replacement on a commercial rooftop unit, start to finish.

Rooftop unit HV1, a Lennox packaged unit on a commercial building in West Covina, had stopped cooling. The condenser coil had a refrigerant leak in a spot that could not be repaired, so brazing was not an option. We quoted a condenser coil replacement, and the coil went in 2 days after the quote, once the customer approved it.

On the day of the condenser coil replacement: old coil out, new coil in, R-410A charge weighed in on the scale and the unit back in service. Return air was 82.4°F and supply air came down to 58.1°F.

JOB FILE · UNIT HV1CLOSED
  • Location: West Covina, Los Angeles County
  • Building: Commercial building, rooftop units
  • Equipment: Lennox packaged rooftop unit, HV1, R-410A
  • Complaint: Unit not cooling
  • Cause: Condenser coil leak in an unrepairable spot
  • Quote: Condenser coil replacement quoted
  • Repair: Coil replaced 2 days after the quote
  • Charge: R-410A weighed in on a scale
  • Result: Return 82.4°F, supply 58.1°F
// Timeline

From a leaking coil to a 24.3°F split.

Every step of this condenser coil replacement, in the order it happened on the roof.

  1. 01 · SEP 5 · THE CALLA rooftop unit not cooling

    Rooftop unit HV1 on a commercial building in West Covina had stopped cooling.

  2. 02 · DIAGNOSISA leak that could not be repaired

    The refrigerant leak was in the condenser coil itself, in a spot that could not be brazed. A coil with a leak like that only gets worse, so we quoted a new condenser coil.

  3. 03 · THE QUOTEWaiting on approval

    The customer took time to approve the quote. The coil was replaced 2 days after the quote went out.

  4. 04 · SEP 5 · 8:39 AM · COIL OUTThe old coil comes off the unit

    We pulled the original condenser coil out of the Lennox unit and set it on the roof.

  5. 05 · 9:45 AM · COIL INNew condenser coil installed

    The new coil went in and was connected to the system.

  6. 06 · 1:20 PM · START-UPSupply air at 58.1°F

    With the R-410A charge weighed in on the scale, the unit came back on. Return air was 82.4°F and supply air came down to 58.1°F, a 24.3°F temperature split.

// Photo by photo

What came out, what went in.

Every photo below is from this condenser coil replacement, in the order the work was done.

01 · SEP 5 · 6:52 AMBefore
Lennox packaged rooftop unit HV1 nameplate, R-410A, on a commercial building in West Covina, California
LENNOX ROOFTOP UNIT · HV1 · R-410A
Original condenser coil with a leak in an unrepairable spot on a Lennox rooftop unit in West Covina
ORIGINAL CONDENSER COIL
02 · SEP 5 · 8:39 AMCoil out, coil in
Old condenser coil removed and set on the roof during a condenser coil replacement in West Covina
OLD COIL OUT, ON THE ROOF
New condenser coil installed in a Lennox rooftop unit during condenser coil replacement in West Covina
NEW COIL INSTALLED
New condenser coil in place on a commercial Lennox rooftop unit in West Covina, California
NEW CONDENSER COIL
03 · SEP 5 · 1:10 PMStart-up
Digital refrigerant scale weighing the R-410A charge into a rooftop unit after condenser coil replacement in West Covina
CHARGE WEIGHED IN
Return air reading of 82.4 degrees on rooftop unit HV1 after condenser coil replacement in West Covina
RETURN AIR · 82.4°F
Supply air reading of 58.1 degrees on rooftop unit HV1 after condenser coil replacement in West Covina
SUPPLY AIR · 58.1°F
04 · SEP 5 · 1:53 PMBack in service
Lennox rooftop unit back in service on the roof after condenser coil replacement in West Covina
UNIT BACK IN SERVICE
// Parts and labor

Everything we did.

When a coil leaks inside, patching it only buys time. A condenser coil replacement keeps a good rooftop unit running for years, at a fraction of the cost of a new unit.

Want coil problems caught early? See our commercial HVAC maintenance agreement, our HVAC installation service or our commercial HVAC services.

WORK COMPLETED · SEP 5DONE
  • Diagnosis of a rooftop unit not cooling
  • Leak found in an unrepairable spot on the coil
  • Original condenser coil removed
  • New condenser coil installed
  • R-410A charge weighed in on a scale
  • Start-up test with return and supply readings
// Rooftop unit not cooling?

A warm store costs sales. Call us first.

Whether it needs a condenser coil replacement, a leak repair or a new board, we diagnose commercial rooftop units and heat pumps across Los Angeles County and the rest of Southern and Central California. See our rooftop unit repair and 24/7 emergency HVAC service. All work is done under California CSLB C-20 license #1155621, and you can verify our license on the CSLB website.

// Condenser coil replacement · FAQ

When does a rooftop unit need a condenser coil replacement?

When the coil leaks in a spot that cannot be repaired, or when it is too corroded to hold refrigerant. Brazing works on a leaking joint, but not inside the coil itself. In that case a condenser coil replacement is the repair that lasts.

Is a condenser coil replacement cheaper than a new rooftop unit?

In most cases, yes. If the compressor and the rest of the unit are in good shape, a condenser coil replacement brings the unit back for a fraction of the cost of replacing the whole rooftop unit.

How long does a condenser coil replacement take?

In this job the coil was replaced 2 days after the quote, once the customer approved it. The swap itself, from the old coil coming out to start-up, was done in one visit.

What readings tell you the repair worked?

The temperature split between return air and supply air. Here return air was 82.4°F and supply air was 58.1°F, a 24.3°F split, which is what a healthy unit should do.

Do you replace condenser coils on commercial rooftop units in my area?

Yes. We service rooftop units for retail stores, offices and property managers across Los Angeles County, the San Gabriel Valley, the Inland Empire, Orange County and the rest of Southern and Central California. See our rooftop unit repair service or check your ZIP code.