Case Study 003 · Commercial · Los Angeles CountyRefrigerant leak repair
on a rooftop unit in West Hollywood.
A rooftop unit at a veterinary hospital had lost all its refrigerant and stopped cooling. The leak was in the condenser coil. Here is the whole refrigerant leak repair, photo by photo, from the bubble test to 53.9°F supply air.
- Same dayLeak found and fixed
- 4.36 lbR-22 weighed in
- 53.9°FSupply air after repair
- 70°FInside the building
Refrigerant leak repair on a commercial rooftop unit, start to finish.
A veterinary hospital in West Hollywood had one rooftop unit that stopped cooling. On the roof, unit HV3 was flat: the refrigerant had leaked out. Oil stains on the condenser coil return bends pointed to the leak, and a bubble test found the exact joints.
We did the refrigerant leak repair the same day: rebrazed the leaking joints, installed a new filter drier and weighed in 4.36 lb of R-22, matching the 4.3 lb on the nameplate. Supply air came down to 53.9°F and the building held 70°F.
- Location: West Hollywood, Los Angeles County
- Building: Veterinary hospital, rooftop units
- Equipment: Carrier packaged rooftop unit, HV3, R-22
- Complaint: Unit not cooling
- Cause: Refrigerant leak at the condenser coil
- Repair: Joints rebrazed, new filter drier
- Charge: 4.36 lb of R-22 weighed in (nameplate 4.3 lb)
- Result: Supply air 53.9°F, building at 70°F
From a flat system to 53.9°F in one day.
Every step of this refrigerant leak repair, in the order it happened on the roof.
- 01 · DEC 10 · THE CALLA rooftop unit not cooling
One of the rooftop units at a veterinary hospital in West Hollywood had stopped cooling its part of the building.
- 02 · 10:54 AM · ON THE ROOFThe system was flat
Unit HV3 had lost its refrigerant. With no charge left, the compressor had nothing to move and the unit could not cool.
- 03 · 12:35 PM · DIAGNOSISThe leak was in the condenser coil
Oil stains on the condenser coil return bends pointed to the leak. A bubble test confirmed it at the coil joints.
- 04 · 1:31 PM · THE REPAIRJoints rebrazed, new drier
We rebrazed the leaking joints and installed a new filter drier, dated 12-10-25 and marked HV3.
- 05 · 3:15 PM · START-UPSupply air at 53.9°F
We weighed in 4.36 lb of R-22, matching the 4.3 lb on the nameplate. Supply air came down to 53.9°F and the thermostat inside read 70°F.
Where it leaked, how we fixed it.
Every photo below is from this refrigerant leak repair, in the order the work was done. The new filter drier is marked with the install date.









Everything we did.
A refrigerant leak repair is only done when the leak is fixed, the system is clean and dry, and the charge is right. That is why we rebraze the leak, change the filter drier and weigh the refrigerant in against the nameplate instead of guessing.
Want leaks like this caught before a unit goes flat? See our commercial HVAC maintenance agreement, the industries we serve or our commercial HVAC services.
- Diagnosis of a rooftop unit not cooling
- Leak search with a bubble test
- Leaking condenser coil joints rebrazed
- New filter drier, dated
- Charge weighed in: 4.36 lb of R-22
- Start-up test and supply air reading
A unit down means a warm building. Call us first.
Whether it is a refrigerant leak repair, a failed board or a bad contactor, we diagnose commercial rooftop units and heat pumps across Los Angeles County and the rest of Southern and Central California. See our rooftop unit repair and 24/7 emergency HVAC service. All work is done under California CSLB C-20 license #1155621, and you can verify our license on the CSLB website.
// Refrigerant leak repair · FAQ
What is refrigerant leak repair on a rooftop unit?
It means finding where the refrigerant is escaping, fixing that exact spot and putting back the right charge. Topping off a leaking unit without fixing the leak only buys a few days or weeks. A real refrigerant leak repair finds the hole first.
How do you find a refrigerant leak?
Oil stains are the first clue, because refrigerant carries compressor oil out with it. In this job the oil on the condenser coil bends pointed to the area, and a bubble test confirmed the exact joints that were leaking.
Can you still repair an R-22 rooftop unit?
Yes. Many older rooftop units in California still run on R-22. When the leak is in a repairable spot, refrigerant leak repair is usually far cheaper than replacing the unit. In this case we fixed the joints and weighed in 4.36 lb of R-22, matching the nameplate.
Why replace the filter drier during a refrigerant leak repair?
Any time a system is opened, moisture and air can get in. A new filter drier catches that moisture before it reaches the compressor, so the repair lasts.
Do you repair commercial rooftop units in my area?
Yes. We service rooftop units for medical offices, veterinary hospitals, retail stores and property managers across Los Angeles County, the San Fernando Valley, Orange County, Ventura County, the Inland Empire and the rest of Southern and Central California. See our rooftop unit repair service or check your ZIP code.