Case Study 002 · Commercial · Los Angeles CountyDefrost board replacement
on a rooftop heat pump in Alhambra.
A rooftop heat pump at a retail store was blowing 82.5°F air. The cause was a failed defrost board that would not let the compressor run. Here is the whole defrost board replacement, photo by photo, from the first reading to 53.4°F supply air.
- One visitDiagnosis and repair
- 82.5°FSupply air on arrival
- 53.4°FSupply air after repair
- 2 partsBoard and contactor
Defrost board replacement on a commercial heat pump, start to finish.
A retail store in Alhambra had one rooftop heat pump that was running but not cooling. On the roof, the supply air on unit HV3 read 82.5°F. The compressor was not running because the main defrost board had failed and was sending the wrong low-voltage signal to the compressor contactor.
We did the defrost board replacement, replaced the pitted compressor contactor in the same visit and started the unit back up in cooling. Return air was 78.6°F and supply air came down to 53.4°F.
- Location: Alhambra, Los Angeles County
- Building: Retail store, rooftop units
- Equipment: ICP packaged heat pump, unit HV3
- Complaint: Unit not cooling
- Reading on arrival: Supply air 82.5°F
- Diagnosis: Failed main defrost board
- Repair: New defrost board and new contactor
- Result: Supply 53.4°F, a 25.2°F split
From 82.5°F to 53.4°F in one visit.
Every step of this defrost board replacement, in the order it happened on the roof.
- 01 · AUG 12 · THE CALLA rooftop unit not cooling
One of the rooftop heat pumps serving a retail store in Alhambra was running but not cooling the sales floor.
- 02 · 4:22 PM · ON THE ROOFSupply air at 82.5°F
The first reading told the story: the air coming out of unit HV3 was 82.5°F, warmer than the air going in. The compressor was not doing its job.
- 03 · DIAGNOSISThe defrost board was the problem
The main defrost board had failed and was sending the wrong low-voltage signal to the compressor contactor, so the compressor would not run. Flipping the board over showed a burned trace on the back.
- 04 · THE REPAIRNew board, new contactor
We replaced the defrost board and the pitted compressor contactor in the same visit. Both new parts are marked with the install date.
- 05 · 5:54 PM · START-UPSupply air at 53.4°F
With the new board in, the compressor came back on. Return air was 78.6°F and supply air dropped to 53.4°F, a 25.2°F temperature split.
What failed, what went in.
Every photo below is from this defrost board replacement, in the order the work was done. New parts are marked with the install date.










Everything we did.
A defrost board replacement is only half the job. The board drives the compressor contactor, so we check that circuit too and replace what is worn while the panel is open. On a commercial roof, that means one visit instead of two.
Want failures like this caught before the store gets hot? See our commercial HVAC maintenance agreement, our heat pump repair service or our commercial HVAC services.
- Diagnosis of a heat pump not cooling
- New main defrost board, dated
- New compressor contactor
- Low-voltage signal checked at the board and contactor
- Start-up test in cooling mode
- Return and supply air readings logged
A warm store costs sales. Call us first.
Whether it turns out to be a defrost board replacement, a contactor or a refrigerant leak, we diagnose commercial rooftop units and heat pumps across Los Angeles County and the rest of Southern and Central California. See our rooftop unit repair and 24/7 emergency HVAC service. All work is done under California CSLB C-20 license #1155621, and you can verify our license on the CSLB website.
// Defrost board replacement · FAQ
What does a defrost board do on a heat pump?
The defrost board controls when a heat pump switches into defrost, and on many units it also passes the low-voltage signal that turns the compressor on. When it fails, the compressor can stop running in cooling mode too, not only in heating.
Can a bad defrost board stop a heat pump from cooling?
Yes. That is exactly what happened in this job. The failed board was sending the wrong low-voltage signal to the compressor contactor, so the compressor would not run and the unit blew 82.5°F air. A defrost board replacement brought the supply air down to 53.4°F.
How do you know the defrost board is the problem?
We check the low-voltage signals going in and out of the board and to the compressor contactor. In this case the board had a burned trace on the back, which confirmed it. A defrost board replacement should always come with that check, so you do not pay for a part you did not need.
Why replace the contactor during a defrost board replacement?
The contactor is what actually switches power to the compressor. This one was pitted, and a pitted contactor is the next part to fail. Replacing it in the same visit saved a second trip to the roof.
Do you repair commercial heat pumps and rooftop units in my area?
Yes. We service commercial rooftop units and heat pumps for retail stores, offices and property managers across Los Angeles County, the San Fernando Valley, Orange County, Ventura County, the Inland Empire and the rest of Southern and Central California. See our rooftop unit repair service or check your ZIP code.