
Case Study 004 · Commercial · Orange CountyLow pressure lockout
on a rooftop unit in Santa Ana.
Stage 1 on a retail store rooftop unit kept locking out on low pressure. The cause was a brass tee someone added instead of fixing a leaking valve. Here is how we found it and put the unit back the way Carrier built it.
- One visitLeak found and fixed
- 9 lbR-407C on stage 1
- 66.3°FSupply air after repair
- 24°FTemperature split
Low pressure lockout on a commercial rooftop unit, start to finish.
A retail store in Santa Ana had one rooftop unit that was not cooling. On the roof, stage 1 of unit HV1 was in a low pressure lockout and nearly flat. Someone before us had screwed a brass tee onto a leaking high-flow valve instead of fixing it, and hung the pressure switch on that tee. The tee has no rubber O-ring, and it leaked the charge out.
We removed the tee, repaired the leak at the high-flow valve, left the pressure switch brazed into the line where Carrier puts it, pulled a vacuum and weighed in 9 lb of R-407C. Return air was 90.3°F and supply air came down to 66.3°F.
- Location: Santa Ana, Orange County
- Building: Retail store, rooftop units
- Equipment: Carrier two-stage rooftop unit, HV1
- On arrival: Stage 1 tripped on low pressure, nearly flat
- Cause: Brass tee added to a leaking high-flow valve
- Repair: Tee removed, leak repaired, vacuum
- Charge: Stage 1: 9 lb of R-407C weighed in
- Result: Return 90.3°F, supply 66.3°F
From a low pressure lockout to a 24°F split in one visit.
Every step of this low pressure lockout repair, in the order it happened on the roof.
- 01 · AUG 31 · THE CALLA rooftop unit not keeping up
One of the rooftop units at a retail store in Santa Ana was not cooling the sales floor.
- 02 · 10:57 AM · ON THE ROOFLocked out on low pressure
Stage 1 on unit HV1 had tripped on low pressure. The circuit was nearly flat.
- 03 · 11:05 AM · DIAGNOSISA brass tee that should not be there
Someone before us had a leaking high-flow valve on this circuit. Instead of fixing it, they screwed a brass tee onto it and hung the pressure switch on the tee. Those tees have no rubber O-ring, and this one leaked the charge out.
- 04 · THE REPAIRBack to the way Carrier built it
We removed the tee, repaired the leak at the high-flow valve and left the pressure switch where it belongs on this unit, brazed into the line. Then we pulled a vacuum on stage 1.
- 05 · 2:19 PM · START-UPSupply air at 66.3°F
We weighed in 9 lb of R-407C on stage 1. With return air at 90.3°F, supply air came down to 66.3°F, a 24°F temperature split.
What was wrong, how we fixed it.
Every photo below is from this low pressure lockout repair, in the order the work was done.










Everything we did.
Clearing a low pressure lockout by adding refrigerant only hides the problem. We find the leak, fix it the right way, remove add-ons that do not belong on the unit, pull a vacuum and weigh in the charge.
Want problems like this caught before a unit locks out? See our commercial HVAC maintenance agreement, our property management HVAC service or our commercial HVAC services.
- Diagnosis of a low pressure lockout on stage 1
- Leaking brass tee removed from the high-flow valve
- Leak at the high-flow valve repaired
- Pressure switch in its factory location, brazed in
- Vacuum pulled on stage 1
- Stage 1 charged: 9 lb of R-407C weighed in
A warm store costs sales. Call us first.
Whether it is a low pressure lockout, a refrigerant leak or a failed board, we diagnose commercial rooftop units across Orange County and the rest of Southern and Central California. See our rooftop unit repair and 24/7 emergency HVAC service. All work is done under California CSLB C-20 license #1155621, and you can verify our license on the CSLB website.
// Low pressure lockout · FAQ
What is a low pressure lockout on a rooftop unit?
The low pressure switch shuts the compressor off when refrigerant pressure drops too far, to protect it. If the unit keeps tripping, the control locks the compressor out. A low pressure lockout almost always means the system is low on refrigerant, and that means a leak.
Why are brass access tees a problem?
They are an add-on, not part of the unit. Many have no rubber O-ring, so the threaded joint seeps refrigerant over time. In this case a tee had been added to avoid fixing a leaking high-flow valve, and it ended up leaking the whole charge out.
Can you just add refrigerant to clear a low pressure lockout?
You can, and the unit will run for a while, but the refrigerant goes right back out through the same leak. A real fix for a low pressure lockout finds the leak, repairs it, pulls a vacuum and weighs in the correct charge.
What is a high-flow valve?
It is the access valve on the refrigerant line where technicians connect their gauges to read pressures. On this Carrier unit the pressures are read from the high-flow valve, and the pressure switch is brazed into the line somewhere else.
Do you service commercial rooftop units in Orange County?
Yes. We service rooftop units for retail stores, offices and property managers across Orange County, Los Angeles County, the Inland Empire and the rest of Southern and Central California. See our Orange County HVAC page or check your ZIP code.
